November 2000 Edition

New Plan Review Requirements

Effective January 1, 2001

In the summer of 1999 the Arizona Automatic Fire Alarm Association, Office of the State Fire Marshal, Cities of Phoenix, Scottsdale, Mesa, Glendale, Surprise Chandler, Gilbert and Central Yavapai District, formed a committee to standardize Plan Review requirements throughout the State of Arizona.

Information was requested from all of the Jurisdictions. When received the information was tabulated and compared. The common requirements were accepted and the others were discussed for clarification. Each item was discussed clarified, adopted or discarded. Some items were only required by one or two jurisdictions but they were very important to them and therefore also adopted. The list was then formulated encompassing the needs of all jurisdictions. Conflicting requirements were discussed while codes and standards were researched until agreements were reached to everyone’s satisfaction.

It is unlikely that any one jurisdiction would require all the information provided. However if we all provide the requested information then we will fulfill the needs of all jurisdictions. This will lead the way in providing the critical information needed to allow our AHJ’s to correctly evaluate each project for Fire Protection needs. Contractors will benefit from having all the information needed to install and maintain the system. Owners will get a complete design package to support their system.

Drawings

Applies to all sheets

First Sheet (Title Sheet)

If insufficient space for Wiring Legend and Symbol List on Title sheet then insert an additional sheet.

Site Plan Sheet

 

Floor Plan Sheets

Additional sheets as required

Riser Diagram Sheet

Details Sheet

Voltage Drop Calculations Sheets

Stand-by Battery Calculation Sheets

All of the above sheets are to be submitted as a complete set of plans for approval.

Approved plans must be kept on site during construction.

Specification Package

TABLE OF CONTENTS (each section shall have tabs and be separated accordingly. Include table of contents.)

1. Fire Alarm Control Panels, Power Supplies and Annunciators

2. Detection Devices

3. Audio/Visual Devices

4. System Components, Modules and Relays

5. Battery Calculations and cut sheets (calcs shall also be on plans)

6. Voltage Calculations (shall also be on plans)

7. Compatibility Listings (matrix, table, or info showing device compatibility)

8. Operating Instructions for entire System

(This will include a copy of what will be posted adjacent to FACP)

9. Manufacturers Inspections Instructions – NFPA Chapter 7

10. NICET Certificate (when required or if prepared by NICET)

As-Built Drawing Cabinet to be Provided

An AS BUILT Drawing Cabinet shall be installed at each project that has a new Fire Alarm System and located where acceptable to the Fire Marshal.

The cabinet shall be tampered and record a supervisory signal at the FACP

The cabinet shall contain the following:

Some of the Endorsing Agencies

Arizona Automatic Fire Alarm Association

Office of the State Fire Marshal

City of Phoenix Fire Department

City of Scottsdale Fire Department

Rural Metro Fire Department

Fountain Hills Fire Department

City of Yuma Fire Department

City of Surprise Fire Department

City of Mesa Fire Department

Central Yavapai Fire District

City of Prescott Fire Department

Sun City Fire Department

City of Kingman Fire Department

City of Tempe Fire Department

Apache Junction Fire Department

 

Additional information will be made available on the web at www.azafaa.org.