1. What is the formal implementation date for submitting standard plans?
  2. January 1, 2001 is the formal implementation date for all standardized plan submittals. This will only apply to those jurisdictions that have adopted the standard format prior to this date. We strongly encourage use of the standard format prior to this date.

  3. Does every jurisdiction in the State require the standard format?
  4. No, not yet. As of August 2000 there are a large number of jurisdictions looking at requiring the format. We hope to include those jurisdictions that require the standard format on the web site at www.azafaa.org. Because the format is so inclusive of reviewer's needs, we do not anticipate any jurisdiction denying the standard format. Several jurisdictions outside of AZ are also looking at the format.

  5. How should the specification booklet be prepared?
  6. The fire alarm specification booklet is required to contain the following information. Each section shall be tabbed and contain the indicated information within each tab.

    1. Fire alarm control panels, power supplies and annunciators

    2. Detection/Initiation Devices (smokes, heat, pull stations, flame detection, etc)

    3. Audio/Visual devices

    4. System components, modules, relays, dialer board, etc.

    5. Battery Calculations and battery cut sheets

    6. Voltage calculations (indicate if they are included on plans)

    7. Compatibility listings (contractors responsibility to show devices are compatible)

    8. Operating instructions for entire system (this includes a copy of what will be posted adjacent to FACP)

    9. Manufacturers inspection requirements/instructions and copy of NFPA Chapter Seven information

    10. NICET or other certificates for responsible designer and lead installers as applicable

  7. How should the tabs be labeled?
  8. Our intent is that the tabs/sections be in the proper sequence. Tabs can be numbered with a front index page, or tabs may be printed with descriptions. AFAA is looking into bulk printing of pre-printed tabs.

  9. How many specification packages shall be prepared?
  10. At minimum the following will be required. One set shall be maintained at the fire alarm control panel (still being standardized), one set shall be provided to the owner prior to final inspection, and at least two sets submitted for review. The returned review sets may meet the other requirements.

  11. What type of binding should be used for the specification package?
  12. At this time the type of binding has not been standardized. This is to allow for flexibility in how the contractors present their material to the AHJ's and owners. Things to keep in mind are; will the specifications be rolled up with the plans so that they do not get lost/separated, three-ring hard binders are very hard to keep with plans, pages shall be secured to binder (not held by pressure binders).

  13. What should be printed on the outside cover of the binder?
  14. We suggest that contractors be creative and promote their companies. We request contractors indicate on the cover that the package meets the AZAFAA submittal standards. This will help AHJ's in the log-in process, and will promote to the owner that your package has been organized to a set of standards.

  15. What is the purpose of section 9, Manufacturers Inspections Instructions?
  16. This section is provided for the building owner/manager along with the field inspector and installer. It provides necessary documentation so the owner can properly maintain the system just installed. A copy of the signal codes for dialers shall also be provided. This information is required to be provided to the owner per NFPA Ch. 7.

  17. Does the AHJ keep specification packages?
  18. This will vary by the AHJ.

  19. Are specification packages required to be present for the inspection?
  20. Yes, specifications are considered part of the system design. They shall be available on site at all times, the same as the approved plans and permit.

  21. Do plans have to be submitted in the exact same format?
  22. Yes. The purpose of a standardized format is that the information is

    organized in such a manor that all parties will know where to look for specific

    information. Guidelines have been established as to what goes on each page. However,

    the exact layout on each of those pages could vary based on unique circumstances. All

    information shall be organized / grouped so that it is clear and legible.

  23. Do all the drawing sheets have to be the same size?
  24. Yes, all drawing sheets shall be the same size.

  25. Can 8-1/2" x 11" drawings be submitted?
  26. No, standard blue print size sheets shall be used. 24" x 36" is preferred.

  27. What should be in the "Scope of Work" section?
  28. This should be a brief summary of what work is taking place. (i.e. is it a new system,

    modification, tenant improvement, ADA upgrade, etc.) Either this section or the

    "Contractor Notes" section should outline who is responsible for hanging the devices,

    pulling wire, etc.

     

     

  29. Does the monitoring company have to be identified on the original submittal package?
  30. Yes, it is understood that the monitoring company might change once turned over to the

    owner. However, this is usually not the case. The approval of the monitoring company

    needs to be addressed during the plan review stage.

  31. Can any symbols be used to identify devices?
  32. No, a standard symbol legend has been adopted and should be used following the formal

    implementation date. If a standard symbol does not exist, than the designer may use their

    own. The main symbol legend should also identify mounting information. See web site.

    Simplified symbol legends may be used on floor plan sheets.

  33. Are contractors using this format currently?
  34. Yes, several contractors have started to adapt to the new format.

  35. Do I have to draw a compete set of plans for a small tenant improvement?
  36. Consult with the respective AHJ for exact requirements. We are looking at standardizing small projects at a later time.

  37. What is the cost of standardized requirements?
  38. None. You are required to prepare the plans prior to the standardization. It is felt by contractors that there will actually be a cost savings when compared to the multiple reviews and uncertainties that currently exist.

  39. Are plans required to be kept with the fire alarm panel?

Yes, all new systems under this standard are required to have a plan/specification box mounted adjacent to the panel, or mounted in an accessible place with the location indicated on the panel. The box shall be keyed the same as the panel, shall be tampered, and capable of holding as-builts, specifications, instructions, maintenance history, low level passwords, software information, and a hard copy of the current program.